Method sheet
Wind Uplift & Edge Attachment Screening
ASCE 7-16 low-rise components & cladding pressures on roof edges (h <= 60 ft, slope <= 7 deg), x2.0 for comparison with ES-1 tested capacity; documentation checklist; tested-assembly matching.
Method
wind-screening 1.2
Engine
1.1.0
Output status
Preliminary - review required
Review
Awaiting review
Formulas
- qh = 0.00256 Kz Kzt Kd Ke V^2 (Eq. 26.10-1), Kd = 0.85
- Kz = 2.01 (z / zg)^(2 / alpha) (Table 26.10-1)
- p = qh [(GCp) + (GCpi)] for outward load; roof zones 2/3, wall zones 4/5 (x0.9 for slope <= 10 deg)
- Wall end-zone width a = min(0.1 x least horizontal dimension, 0.4h), not less than 0.04 x least horizontal dimension or 3 ft
- Design pressure = p x 2.0 (ES-1)
Conventions
- Edition, jurisdiction, risk category and wind speed source are recorded with every result.
Limits - what it will not do
- ASCE 7-16 only; other editions are refused.
- No fastener spacing and no "meets wind" statement.
- A capacity is shown only for an exact match to a signed ES-1 test record; AFS has none loaded yet.
- Exposure B below 30 ft is held at z = 30 ft (the ASCE 7-10 rule, kept as a conservative choice; ASCE 7-16 permits 15 ft). The reviewing engineer decides.
- A parapet coping is evaluated at the parapet top height (ASCE 7-16 section 30.8): enter that height. Parapet zone relief is not applied.
- Values marked Likely in the research (Exposure B/D alpha and zg; the wall 10% reduction) need PE confirmation.
Who must review it
- Licensed structural engineer (PE): method, coefficients and applicability
Worked example
Inputs 115 mph, Exposure C, h = 60 ft, enclosed
Expected qh 32.7 psf; corner design 221.1 psf vertical, 94.2 psf horizontal
Checked by an automated test on every change.
Sources
- ASCE/SEI 7-16 Minimum Design Loads and Associated Criteria for Buildings and Other Structures - American Society of Civil Engineers, read 2026-10-16
Eq. 26.10-1, Tables 26.6-1, 26.10-1, 26.11-1, 26.13-1, Figures 30.3-1 and 30.3-2A. Verify the edition the jurisdiction has adopted.
- ANSI/SPRI/FM 4435/ES-1 Test Standard for Edge Systems Used with Low Slope Roofing Systems - SPRI, read 2026-10-16
RE-2 face test for fascia, RE-3 coping test; tested capacity compared with design pressure x 2.0. A test record covers one exact assembly.