Occupant Load, Egress & Accessibility Screening
Occupant load from floor areas and user-entered area-per-occupant factors; egress capacity width from a user-entered width per occupant; number of exits from user-entered occupant-load thresholds; ramp running slope against 1:12. Not a code determination.
Method
code-occupancy 1.1
Engine
1.1.0
Output status
Preliminary - review required
Review
Awaiting review
Formulas
- Space load = floor area / area per occupant (factor entered by the user from the adopted code, e.g. IBC Section 1004)
- Round up per space (default): total = sum of ceil(space load); otherwise total = ceil(sum of space loads)
- Egress capacity width = total occupants x width per occupant (entered, e.g. from IBC Section 1005), stairways and other components separately
- Exits = the user threshold row with the largest starting load at or below the total (thresholds entered, e.g. from IBC Section 1006)
- Ramp: running slope compared with 1:12 (2010 ADA Standards 405.2), reusing geometry-conversion/1.0
Conventions
- Area and area per occupant are in the same unit (ft² or m²).
- Width per occupant is in inches (or mm) per occupant.
- Every factor carries the source the user gave.
Limits - what it will not do
- This is not a code determination: no code table is built in and no requirement is checked except the arithmetic on the entered factors.
- Mixed-use rules, minimum widths, exit separation, travel distance, common path, single-exit spaces and stories are not checked.
- Accessibility: ramp running slope only. Cross slope, rise, landings, handrails and every other accessibility requirement are not checked.
Who must review it
- Licensed architect or code consultant: confirm the method against the adopted building code
- Building official (AHJ): occupant loads, egress and accessibility for the project
Worked example
Inputs Spaces 5,000 ft² / 100, 1,210 ft² / 15, 310 ft² / 7; 0.3 and 0.2 in per occupant; thresholds from 1: 1, from 50: 2, from 501: 3; ramp 30 in over 30 ft
Expected 176 occupants rounded per space (175 rounded once); 52.8 in stairways, 35.2 in other components; 2 exits; ramp 1:12, within
Checked by an automated test on every change.
Sources
- Occupant load, egress width and exit count arithmetic - Method sheet code-occupancy/1.0, read 2026-10-16
Occupant load = floor area / area per occupant, per space, rounded up per space when the code requires it; egress width = occupants x width per occupant; exits from the user-entered thresholds. Every factor is entered by the user from the adopted code.
- 2021 International Building Code, Chapter 10 Means of Egress (free read-only text) - International Code Council, read 2026-10-16
Section 1004 (occupant load), Section 1005 (egress width) and Section 1006 (number of exits). Read the factor for the space at its source; no value from the code is reproduced in this tool. Verify the edition the jurisdiction has adopted and its local amendments.
- 2024 International Building Code, Chapter 10 Means of Egress (free read-only text) - International Code Council, read 2026-10-16
The 2024 edition of the same chapter, for jurisdictions that have adopted it.
- ADA Accessibility Standards, 405 Ramps - U.S. Access Board, read 2026-10-16
The Access Board publication of the 2010 ADA Standards, at section 405 Ramps (405.2 Slope). The ramp check covers running slope only.
- 2010 ADA Standards for Accessible Design, 405.2 Slope - U.S. Department of Justice, read 2026-10-16
Ramp runs shall have a running slope not steeper than 1:12. Used here as a reference check of one provision only, not a code compliance determination.