Defects that turn up on a flashing punch walk
MBCI says to check roof panel joints and trims for proper seals and loose fasteners.
Drexel's Econo Coping guide has a nail in each pre-punched hole of the cleat.
Drexel's Econo Coping guide has the roof-side leg of each coping length screwed with #9-13x1-1/2" S.S. washered screws at 12" on center.
Section through a parapet wall capped by a red AFS coping cap whose hems curl inside and hook below a continuous cleat on each wall face. Seven lettered checks: nails in every pre-punched hole, cleat present and tight, a 1/8 inch gap between cleat sections, the lap in place with no gap between coping lengths, sealant at a lap or end continuous, an undamaged finish, and washered screws through the roof-side leg. A side view shows two coping lengths lapped and two cleat sections with the gap. Five small caps show both hems open, both closed, one open and one closed, a kick edge with the hem open, and a kick edge with the hem closed.
- A
- A nail in every pre-punched hole of the cleat
- B
- Cleat present and tight to the wall
- C
- 1/8 in gap between cleat sections only, for thermal movement
- D
- Coping lengths lapped over the notched end, with no gap between them
- E
- Sealant at a lap or end where the specification calls for it, continuous with no gaps
- F
- Finish undamaged, with no repair marks
- G
- Washered screws through the roof-side leg, 12 in on center (Drexel guide)