Fascia LT installation sequence
ANSI/SPRI/FM 4435/ES-1 edge system: 22 Gauge Cont Cleat, Snap-On Cover, 10' Lengths. 3", 4.5", 6", 8" faces.
This sequence follows Drexel Metals' published installation guide for the system. The project's specifications, the approved shop drawings and the roofing membrane manufacturer's requirements govern; where they differ, follow them and ask AFS. Source: Drexel Metals, “Installation Guide for Fascia Cover LT”.
Step 1 of 4
Installing 22GA Galvanized Cleat
- Apply water cut-off mastic and place the face of the cleat squarely on the edge of the roof membrane, over the wood nailing plate.
- Press it firmly into position and screw through the pre-punched face holes.
- At a miter, miter-cut the cleat into the corner as required to keep a continuous cleat line, then fasten at a minimum 6" in each direction from the corner, or closer at special conditions.
- Butt the cleat ends and apply tube sealant over the butted ends.
As printed in the Drexel guide
“screw through the pre-punched face holes with #10-13x1" S.S. Panhead Woodscrews provided.”
Common mistakes this step guards against
- Do not leave butted cleat ends unsealed - apply tube sealant over them.
- Do not break the cleat line at a corner - miter-cut it so the line stays continuous.
Parts, lettered as in the guide
- AFascia Cover LT Flashing 10'-0" Std. Lengths
- BFascia Cover LT Splice Plate 6" Lengths
- C22GA Continuous LT Cleat 10'-0" Lengths
- DFascia Cover LT Miter (Outside Corner Shown)
- E#10-13x1" S.S. Panhead Woodscrew at 12" o.c. (6" from ends) (Included & Required)
- FApproved Roofing Membrane (By Installer)
- -Water Cut Off Mastic Shown under the cleat face
- -Tube Sealant Shown at splice plates and butted cleat ends
Field checklist
Fascia LT - from Drexel's guide. Tick each item as it is done; print this page for the crew.
Common mistakes
Each line is the reverse of an instruction the Drexel guide states.
- Do not leave butted cleat ends unsealed - apply tube sealant over them. (step 1)
- Do not break the cleat line at a corner - miter-cut it so the line stays continuous. (step 1)
- Do not butt lengths tight - leave the 1/8" gap for thermal expansion. (step 4)
- Do not leave a joint without a splice plate. (step 4)
- Do not cut lengths that leave short sections next to each other. (step 4)
Notes printed on the guide
- Isolate all metal parts from ACQ-treated wood, or any other galvanically incompatible material, with an appropriate membrane.
- Appliance attachments - lightning rods, signs, antennae - that penetrate the water seal, set up a galvanic reaction or otherwise compromise the roof edge system are to be eliminated or isolated, per section 8.0 of ANSI/SPRI ES-1. Isolate appliances from the edge system or do not attach them to it; the lightning protection manufacturer gives the attachment instructions.
Printed on the section detail
- Face height 8" max. / 3" min. (Fascia Cover LT print approval DM-15488)
- #10-13x1" S.S. Panhead Woodscrew 12" on center through pre-punched cleat hole and membrane
- Water cut-off mastic under the cleat face
Drexel published ratings
Sustained pressure as Drexel publishes it (Drexel Metals DM-19063 "ES-1_GT-1 Certification Program Product Line Card" 12.09.25). Design Engineer must apply the Factor of Safety.
| Cover | Face up to | Wall up to | Cleat | Sustained pressure |
|---|---|---|---|---|
| 24 gauge | 8" | - | 22 ga | -210 psf |
| .040 AL | 6" | - | 22 ga | -180 psf |