High wind and extreme weather systems · Lesson 3 of 4

High wind and extreme weather systems: methods and worked application

A six-step screening method, a fully worked example for a parapet coping, how velocity pressure grows with the square of speed, two pressure bases, where a manufacturer value fits, a second example from SPRI, and the limits of the screening.

You will be able to: Carry a documented wind screening for one roof edge from site facts to demand numbers, show two safety-factor bases, set a manufacturer's published value beside the result without a verdict, and decide what the engineer must be handed.

12 min · 11 slides · 9 questions

All lessons in this module
Slide 1 of 11

The screening method in six steps

A documented screening goes from site facts to numbers the engineer of record can check:

  • Site facts: location, risk category, height, exposure
  • Adopted ASCE 7 edition and basic wind speed
  • Velocity pressure from speed, height, exposure
  • Roof zones, coefficients and internal pressure
  • Pressures on the basis the engineer chooses
  • Hand-off: tornado check, tested assembly, gaps
The screening method in six stepsA vertical flow of six navy boxes joined by green arrows. 1 Site facts. 2 Edition and basic wind speed from the local authority. An amber caution box: stop if the job is ASCE 7-22, a slope over 7 degrees or a roof over 60 feet, which needs the engineer's analysis. 3 Velocity pressure q. 4 Roof zones and coefficients. 5 Pressures on a basis. 6 Hand-off to the engineer.The screening method in six steps1Site factslocation, risk category, height, exposure2Edition and basic wind speedfrom the local authorityStop if the job is ASCE 7-22,a slope over 7 degrees or a roofover 60 ft: engineer's analysis3Velocity pressure qspeed squared, height, exposure4Roof zones and coefficientsperimeter, corner, internal pressure5Pressures on a basisstrength level, ASD, safety factor6Hand-off to the engineertornado check, tested assembly, gaps

A vertical flow of six navy boxes joined by arrows. 1 Site facts. 2 Edition and basic wind speed from the local authority. An amber caution box says to stop if the job is ASCE 7-22, a slope over 7 degrees or a roof over 60 feet. 3 Velocity pressure q. 4 Roof zones and coefficients. 5 Pressures on a basis. 6 Hand-off to the engineer.

1
Site facts: location, risk category, mean roof height and exposure
2
The adopted ASCE 7 edition and basic wind speed from the jurisdiction, never a storm category
3
Velocity pressure from the speed squared, the height and the exposure
4
Roof zones and coefficients, with internal pressure for enclosed or partially enclosed buildings
5
Pressures on the basis the engineer chooses: strength level, allowable stress or a safety factor
6
Hand-off: tornado check, tested assembly, substrate and what AFS cannot confirm
The order the AFS screening method follows, from the ASCE 7-16 low-rise method. The amber box is the screening's own limit: outside it the engineer of record's analysis is needed.

Videos for this lesson

What this video shows: A SOPREMA technical support manager demonstrates, per its description, how to calculate wind design pressures for low-slope roofing using ASCE 7-16. It is a roofing membrane maker's walk through the method, not about edge metal.

Video: Low Slope Roofing Wind Design: ASCE 7-16 Calculations by SOPREMA USA, on YouTube. Chosen from the video's published description.

Glossary

Velocity pressure (qh)
The wind pressure at roof height, 0.00256 x Kz x Kzt x Kd x Ke x V squared in psf with V in mph; it grows with the square of the speed.
Kz
The velocity pressure exposure coefficient, which depends on the terrain exposure and the height above ground; the AFS screening gives 0.982 for Exposure C at 30 ft.
Kd
The wind directionality factor, 0.85 for components and cladding in SPRI's examples.
Ke
The ground elevation factor added in ASCE 7-16; SPRI notes that 1.00 is a permitted conservative value.
Strength level
The wind load from the map speed used with strength design; allowable stress design takes 0.6 times it.
Allowable stress design (ASD)
A design basis that applies a 0.6 factor to the ASCE 7-16 strength-level wind result, as SPRI describes.
Basis A and basis B
The two pressure presentations the AFS screening shows: strength level times 2.0, and strength level times 0.6 times 2.0. The engineer of record chooses.
Tested assembly
The exact product, metal, gauge, cleat, splice and fastener spacing that an accredited lab tested to ES-1; a capacity statement is only valid for that assembly.