Three tiers of proof
Air-leakage proof comes in three tiers: a material, an assembly of materials, and the whole building.
The 2021 IECC prints the limits on these slides in cfm/ft2 and in L/(s·m2), at a pressure difference of 75 Pa (0.3 in. w.g.).
Each tier is ten times looser than the one before it.
Dot plot on a logarithmic axis, cfm per square foot at 75 Pa: material 0.004, assembly 0.04, whole building 0.40, and a diagnostic range from 0.40 to 0.60. Each tier is ten times the one before. Metric equivalents are 0.02, 0.2, 2.0 and 2.0 to 3.0 L/(s per square meter).
Sources
- Significant Changes to the International Energy Conservation Code, 2021 Edition - C402.5 Air Leakage (excerpt) - International Code Council