Defects at openings and lintels
Without end dams, water a flashing collects at a lintel can run off its ends and into the wall.
IMI asks whether end dams are at or beyond the end of veneer lintels.
BSD-013 says leaks often occur at lapped joints of rigid flashing, and that these should be sealed, not just lapped.
BIA Technical Note 7 says to lap continuous flashing at least 6 in and seal with compatible sealant or adhesive.
Two elevations of a steel lintel. Correct: flashing past the lintel with turned-up end dams, a 6 inch sealed lap, weeps above and a drip beyond the face. Incorrect: flashing cut flush with no end dams, a short unsealed lap, weeps far apart or blocked, the flashing stopping short of the wall face with no drip, and the flashing sagging.
- P
- Flashing cut flush, with no end dams: water runs off the ends into the wall
- Q
- Short, unsealed lap between pieces
- R
- Flashing stops short of the wall face with no drip, so water can wick back under it
- S
- Weeps far apart or blocked with mortar
- T
- Flashing sagging because it is not supported
Sources
- Technical Note 7: Water Penetration Resistance, Design and Detailing (November 2017) - Brick Industry Association
- Flashing Installation Checklist (Rev. November 2022) - International Masonry Institute
- BSD-013: Rain Control in Buildings (John Straube, 2011-08-22) - Building Science Corporation