Structural attachments and substrate assessment · Lesson 2 of 4

Structural attachments and substrate assessment: materials, standards and design constraints

The IBC and SPRI path by edition, the wood properties that set withdrawal resistance, treated wood and fastener metals, and why masonry anchor capacity is product-specific data.

You will be able to: Name the code path and standards that govern roof-edge attachment by edition, explain how wood density, moisture, grain and fastener type change what a nailer holds, choose fastener metals for treated wood, and read a masonry anchor evaluation report.

14 min · 12 slides · 11 questions

All lessons in this module
Slide 1 of 12

The code path by edition

In the 2012 IBC, section 1504.5 required metal edge securement on low-slope built-up, modified bitumen and single-ply roofs, except gutters, to be tested to RE-1, RE-2 and RE-3 of ES-1.

SPRI says nothing changed in 2015, and that in 2018 the test reference became ANSI/SPRI/FM 4435/ES-1.

Always name the IBC edition your jurisdiction adopted.

Videos for this lesson

What this video shows: An American Wood Council presentation of about an hour and a half on nailed, screwed and bolted connections, including withdrawal capacity, tabulated and calculated methods, and wood-to-steel and wood-to-concrete connections. It is based on the 2015 edition of the NDS, so check the provisions of the edition in force. Checked against the video's description.

Video: 2015 NDS Connections Primer by American Wood Council, on YouTube. Chosen from the video's published description.

Glossary

Specific gravity (G)
A wood density index. The Wood Handbook withdrawal equations define it on ovendry weight and volume at 12 percent moisture content; the NDS uses ovendry weight and volume, so the two bases differ slightly and results mixing them are indicative.
Withdrawal resistance
How much axial pull a fastener can take before it comes out of the wood; it depends on wood density, fastener diameter and depth of penetration.
Maximum load versus design value
A maximum load is the highest load a short-time test reached; design values are reduced from it for variability, duration of load and safety.
Use Category
AWPA's class for treated wood by exposure, for example UC1 interior dry, UC3B above ground and UC4A ground contact.
Special inspection
Inspection of an installed anchor required by an evaluation report under IBC sections 1704 and 1705, checking items such as anchor type, embedment, spacing and edge distance.