The method in nine steps
The method is a steady-state screen: it compares the temperature of the first condensing surface with the indoor dew point.
The designer of record owns each step; the diagram shows the order and where a hygrothermal analysis takes over.
The inputs below are examples for teaching, not project data.
Nine boxes in three rows. Steps 1 to 4 record the code, indoor conditions, dew point and outdoor design temperature. Step 5 computes the sheathing temperature and step 6 asks whether it is above the dew point. No leads to step 7, choosing controls; yes goes to step 8, the summer and inward check. Step 9 escalates special cases and writes the packet.
- 1
- Record the jurisdiction, adopted code editions and climate zone
- 2
- Set the indoor temperature and humidity, with their basis
- 3
- Work out the indoor dew point (the frost point if it is below freezing)
- 4
- Set the outdoor design temperature, the average of the coldest three months
- 5
- Find the first condensing surface and its temperature by the R ratio
- 6
- Compare with the dew point and record the margin
- 7
- If at or below: choose controls (warm the surface, keep air away, a suitable retarder, lower humidity)
- 8
- Check the summer and inward case
- 9
- Escalate special-use or inward-drive cases to a hygrothermal analysis and write the packet
Sources
- Condensation Control in Walls - Cold Weather (last updated 2021-09-26) - US DOE Building America Solution Center (PNNL)
- Building Science Digest 163: Controlling Cold-Weather Condensation Using Insulation (effective November 15, 2011) - Building Science Corporation (John Straube)
- Design Center: Wall and roof assembly R-value, U-factor and dew point (steady-state screening tool) - Architectural Flashing Supply